Catalog
Commercial Immersion and Surface Mounted Energy Saver Electric Water Heaters
Bradford White® Electric Commercial Water Heaters
Unit of Measure
Items |
/Asset/a1406.jpg M-II-50A-6-3SF Commercial Immersion and Surface Mounted Energy Saver Electric Water Heaters |
/Asset/a1406.jpg M-II-50A-9-3SF Commercial Immersion and Surface Mounted Energy Saver Electric Water Heaters |
/Asset/a1406.jpg M-II-50A-12-3SF Commercial Immersion and Surface Mounted Energy Saver Electric Water Heaters |
/Asset/a1406.jpg M-II-50A-13.5-3SF Commercial Immersion and Surface Mounted Energy Saver Electric Water Heaters |
/Asset/a1406.jpg M-II-50A-15-3SF Commercial Immersion and Surface Mounted Energy Saver Electric Water Heaters |
|||||
Manufacturer | N/A Bradford White® | |||||||||
Available Voltage | N/A 208 V240 V277 V380 V415 V480 V600 V | |||||||||
Capacity | N/A 50 U.S. gal42 Imp. gal189 L | |||||||||
Schematic |
N/A
Schematic Drawing for Commercial Immersion and Surface Mounted Energy Saver Electric Water Heaters |
|||||||||
Height A | N/A 47-3/4 in1213 mm | |||||||||
Jacket Diameter B | N/A 24 in610 mm | |||||||||
Height to T and P Connection C | N/A 41 in1041 mm | |||||||||
Floor to Hot Water Outlet D | N/A 49-1/4 in1251 mm | |||||||||
Floor to Cold Water Inlet E | N/A 6-3/4 in178 mm | |||||||||
Floor to Top of Control Box F | N/A 46-1/2 in1181 mm | |||||||||
Standard Approximate Shipping Weight | N/A 270 lb122 kg | |||||||||
ASME Approximate Shipping Weight | N/A 302 lb137 kg | |||||||||
Input Power | N/A 6 kW | N/A 9 kW | N/A 12 kW | N/A 13.5 kW | N/A 15 kW | |||||
Number of Elements 208 V Single Phase (Fused Models) | N/A 3(2) | N/A 3 | N/A 3 | N/A 3 | N/A 3 | |||||
Number of Elements 208 V Three Phase (Fused Models) | N/A 3 | |||||||||
Number of Elements 240 V Single Phase (Fused Models) | N/A 3(2) | N/A 3 | N/A 3(2) | N/A 3 | N/A 3 | |||||
Number of Elements 240 V Three Phase (Fused Models) | N/A 3 | |||||||||
Number of Elements 277 V Single Phase (Fused Models) | N/A 3 | |||||||||
Number of Elements 380 V Three Phase (Fused Models) | N/A 3 | |||||||||
Number of Elements 415 V Three Phase (Fused Models) | N/A 3 | |||||||||
Number of Elements 480 V Single Phase (Fused Models) | N/A 3(2) | N/A 3 | N/A 3(2) | N/A 3 | N/A 3 | |||||
Number of Elements 480 V Three Phase (Fused Models) | N/A 3 | |||||||||
Number of Elements 600 V Three Phase (Fused Models) | N/A 3 | |||||||||
Full Load Current Single Phase 208 V | N/A 28.8 A | N/A 43.2 A | N/A 57.6 A | N/A 64.9 A | N/A 72.1 A | |||||
Full Load Current Three Phase 208 V | N/A 16.6 A | N/A 25.0 A | N/A 33.3 A | N/A 37.5 A | N/A 41.6 A | |||||
Full Load Current Single Phase 240 V | N/A 25 A | N/A 37.2 A | N/A 50 A | N/A 56.2 A | N/A 62.5 A | |||||
Full Load Current Three Phase 240 V | N/A 14.4 A | N/A 21.6 A | N/A 28.9 A | N/A 32.5 A | N/A 36.1 A | |||||
Full Load Current Single Phase 277 V | N/A 21.6 A | N/A 32.4 A | N/A 43.3 A | N/A 48.7 A | N/A 54.1 A | |||||
Full Load Current Three Phase 380 V | N/A 10 A | N/A 14 A | N/A 19 A | N/A 21 A | N/A 23 A | |||||
Full Load Current Three Phase 415 V | N/A 9 A | N/A 13 A | N/A 17 A | N/A 19 A | N/A 21 A | |||||
Full Load Current Single Phase 480 V | N/A 12.5 A | N/A 18.7 A | N/A 25 A | N/A 28.1 A | N/A 31.2 A | |||||
Full Load Current Three Phase 480 V | N/A 7.2 A | N/A 10.8 A | N/A 14.4 A | N/A 16.2 A | N/A 18.0 A | |||||
Full Load Current Three Phase 600 V | N/A 5.8 A | N/A 8.7 A | N/A 11.5 A | N/A 13 A | N/A 14.4 A | |||||
Recovery at 40 ºF Temperature Rise | N/A 62 gal/h | N/A 93 gal/h | N/A 124 gal/h | N/A 140 gal/h | N/A 155 gal/h | |||||
Recovery at 50 ºF Temperature Rise | N/A 50 gal/h | N/A 74 gal/h | N/A 99 gal/h | N/A 112 gal/h | N/A 124 gal/h | |||||
Recovery at 60 ºF Temperature Rise | N/A 41 gal/h | N/A 62 gal/h | N/A 83 gal/h | N/A 93 gal/h | N/A 103 gal/h | |||||
Recovery at 70 ºF Temperature Rise | N/A 35 gal/h | N/A 53 gal/h | N/A 71 gal/h | N/A 80 gal/h | N/A 89 gal/h | |||||
Recovery at 80 ºF Temperature Rise | N/A 31 gal/h | N/A 47 gal/h | N/A 62 gal/h | N/A 70 gal/h | N/A 78 gal/h | |||||
Recovery at 90 ºF Temperature Rise | N/A 28 gal/h | N/A 42 gal/h | N/A 55 gal/h | N/A 62 gal/h | N/A 69 gal/h | |||||
Recovery at 100 ºF Temperature Rise | N/A 25 gal/h | N/A 37 gal/h | N/A 50 gal/h | N/A 56 gal/h | N/A 62 gal/h | |||||
Recovery at 120 ºF Temperature Rise | N/A 21 gal/h | N/A 31 gal/h | N/A 41 gal/h | N/A 47 gal/h | N/A 52 gal/h | |||||
Recovery at 140 ºF Temperature Rise | N/A 18 gal/h | N/A 27 gal/h | N/A 35 gal/h | N/A 40 gal/h | N/A 44 gal/h | |||||
Type | N/A Electric | |||||||||
Style | N/A Immersion T-Stat with Connection | |||||||||
Size | N/A C | |||||||||
Industry Standards | N/A ASME Certified CSA® Certified ETL NSF | |||||||||
General Information |
N/A
All electric water heaters are certified at 300 psi test pressure (2068 kPa) and 150 psi working pressure (1034 kPa). All models are design certified by ETL, for up to 180 ºF (82 ºC) application as an Automatic Storage Heater, and an Automatic Circulating Tank Heater. As an Automatic Storage Heater, all models are complete, self-contained water heating systems. It needs no separate storage tank, pump, wiring or elaborate piping network. When equipped with a mixing valve, it will supply 180 ºF (82 ºC) sanitizing and lower temperature general purpose hot water simultaneously. These models can be used either as a single unit or in multiples connected in series or parallel (recommended). Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement. |
|||||||||
Features |
N/A
The Immersion and Surface Mounted Electric Models Feature:
|
|||||||||
Warranty |
N/A
|
|||||||||
Note |
N/A
Units with amperage draw of 48 amps or more require factory installed internal fusing. Optional surface thermostats ranging from 80 ºF to 140 ºF are available. Meet or exceed ASHRAE 90.1b (current standard) C.E.C. Listed. If the number of elements on non-fused models is different, it is located in parentheses ( ), following the amp draw. |
N/A
Units with amperage draw of 48 amps or more require factory installed internal fusing. Optional surface thermostats ranging from 80 ºF to 140 ºF are available. Meet or exceed ASHRAE 90.1b (current standard) C.E.C. Listed. |
N/A
Units with amperage draw of 48 amps or more require factory installed internal fusing. Optional surface thermostats ranging from 80 ºF to 140 ºF are available. Meet or exceed ASHRAE 90.1b (current standard) C.E.C. Listed. If the number of elements on non-fused models is different, it is located in parentheses ( ), following the amp draw. |
N/A
Units with amperage draw of 48 amps or more require factory installed internal fusing. Optional surface thermostats ranging from 80 ºF to 140 ºF are available. Meet or exceed ASHRAE 90.1b (current standard) C.E.C. Listed. |
N/A
Units with amperage draw of 48 amps or more require factory installed internal fusing. Optional surface thermostats ranging from 80 ºF to 140 ºF are available. Meet or exceed ASHRAE 90.1b (current standard) C.E.C. Listed. |
|||||
|