Catalog
Unit of Measure

Specifications

Manufacturer

N/A Bradford White®

Available Voltage

N/A 208 V240 V277 V380 V415 V480 V600 V

Capacity

N/A 120 U.S. gal100 Imp. gal450 L

Standard Approximate Shipping Weight

N/A 430 lb195 kg

ASME Approximate Shipping Weight

N/A 485 lb220 kg

Input Power

N/A 30 kW

Type

N/A Electric

Style

N/A Immersion T-Stat with Connection

Size

N/A C

Industry Standards

N/A ASME Certified CSA® Certified ETL NSF

Dimensions

Schematic

N/A
Schematic Drawing for Commercial Immersion and Surface Mounted Energy Saver Electric Water Heaters

Height A

N/A 64-1/2 in1638 mm

Jacket Diameter B

N/A 30-1/4 in768 mm

Height to T and P Connection C

N/A 55 in1397 mm

Floor to Hot Water Outlet D

N/A 66 in1676 mm

Floor to Cold Water Inlet E

N/A 6-3/4 in178 mm

Floor to Top of Control Box F

N/A 50-1/4 in1276 mm

Electrical Characteristics

Number of Elements 208 V Single Phase (Fused Models)

N/A 6

Number of Elements 208 V Three Phase (Fused Models)

N/A 6

Number of Elements 240 V Single Phase (Fused Models)

N/A 6

Number of Elements 240 V Three Phase (Fused Models)

N/A 6

Number of Elements 277 V Single Phase (Fused Models)

N/A 6

Number of Elements 380 V Three Phase (Fused Models)

N/A 6

Number of Elements 415 V Three Phase (Fused Models)

N/A 6

Number of Elements 480 V Single Phase (Fused Models)

N/A 6

Number of Elements 480 V Three Phase (Fused Models)

N/A 6

Number of Elements 600 V Three Phase (Fused Models)

N/A 6

Full Load Current Single Phase 208 V

N/A 144.2 A

Full Load Current Three Phase 208 V

N/A 83.3 A

Full Load Current Single Phase 240 V

N/A 125 A

Full Load Current Three Phase 240 V

N/A 72.2 A

Full Load Current Single Phase 277 V

N/A 108.3 A

Full Load Current Three Phase 380 V

N/A 46 A

Full Load Current Three Phase 415 V

N/A 42 A

Full Load Current Single Phase 480 V

N/A 62.5 A

Full Load Current Three Phase 480 V

N/A 36.1 A

Full Load Current Three Phase 600 V

N/A 28.9 A

Maximum Recovery

Recovery at 40 ºF Temperature Rise

N/A 310 gal/h

Recovery at 50 ºF Temperature Rise

N/A 248 gal/h

Recovery at 60 ºF Temperature Rise

N/A 207 gal/h

Recovery at 70 ºF Temperature Rise

N/A 177 gal/h

Recovery at 80 ºF Temperature Rise

N/A 155 gal/h

Recovery at 90 ºF Temperature Rise

N/A 138 gal/h

Recovery at 100 ºF Temperature Rise

N/A 124 gal/h

Recovery at 120 ºF Temperature Rise

N/A 103 gal/h

Recovery at 140 ºF Temperature Rise

N/A 89 gal/h

General Information

General Information

N/A All electric water heaters are certified at 300 psi test pressure (2068 kPa) and 150 psi working pressure (1034 kPa). All models are design certified by ETL, for up to 180 ºF (82 ºC) application as an Automatic Storage Heater, and an Automatic Circulating Tank Heater. As an Automatic Storage Heater, all models are complete, self-contained water heating systems. It needs no separate storage tank, pump, wiring or elaborate piping network. When equipped with a mixing valve, it will supply 180 ºF (82 ºC) sanitizing and lower temperature general purpose hot water simultaneously. These models can be used either as a single unit or in multiples connected in series or parallel (recommended).
Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.

Features

Features

N/A The Immersion and Surface Mounted Electric Models Feature:
  • Surface Mounted Thermostat Step Control (modulation) - Can be accomplished by variable setting on thermostats (each element has an individual thermostat and high limit).
  • Immersion Thermostats - Immersion type for accurate temperature control from up to 180 ºF (82 ºC) with manual reset high limit control.
  • 3" (76 mm) Non-CFC foam insulation - Covers the sides and top of tank, reducing the amount of heat loss. This results in less energy consumption, improved operation efficiencies and jacket rigidity.
  • Factory Installed Hydrojet® Sediment Reduction System - Cold water inlet sediment reducing device helps prevent sediment build up in the tank.
  • Vitraglas® Lining - Bradford White tanks are lined with an exclusively engineered enamel formula that provides superior tank protection from the highly corrosive effects of hot water. This formula (Vitraglas®) is fused to the steel surface by firing at a temperature of over 1600 ºF (871 ºC).
  • Water Connections - 1 1/2" NPT factory installed true dielectric fittings extend water heater life and eases installation.
  • Elements - Screw in style. Surface mounted thermostat models have elements made of nickel chromium wire embedded in magnesium oxide, sheathed in copper and electroplated to minimize degradation of the anode. Incoloy sheathed elements are optional (Incoloy elements are standard for all 600 volt models). Immersion thermostat models have low watt density incoloy sheathed elements standard which resists burnout caused by dry fire or lime buildup.
  • Two Magnesium Anode Rods - Provide added protection against corrosion for long trouble free service.
  • Hand Hole Cleanout - Allows inspection of tank interior and facilitates the removal of sediment deposits.
  • ASME Construction Available.
  • NSF Construction Available.
  • Low Restriction Brass Drain Valve - Durable tamper proof design.
  • T&P Relief Valve - Installed.
  • Completely Pre-wired - With pressure lug terminal block eliminating need for splicing or taping of wires.
  • Voltages Available - 208 V, 240 V, 277 V, 380 V, 415 V, 480 V and 600 V.

Warranty

Warranty

N/A
  • 3-Year Limited Warranty - On Inner Glass-Lined Tank.
  • 1-Year Limited Warranty - On all Other Component Parts.

Note

Note

N/A Units with amperage draw of 48 amps or more require factory installed internal fusing.

Optional surface thermostats ranging from 80 ºF to 140 ºF are available.

Meet or exceed ASHRAE 90.1b (current standard) C.E.C. Listed.