                                                                                Manufacturer | 
                                                                        N/A State® | 
                                                                                Nominal Storage Capacity | 
                                                                        N/A 200 U.S. gal | 
                                                                                Input Power | 
                                                                        N/A 800000 BTU/hr | 
                                                                                First Hour Rating | 
                                                                        N/A 936 gal | 
                                                                                Shipping Weight with Burner | 
                                                                        N/A 2103 lb | 
                                                                                Motor Power | 
                                                                        N/A 1/3 hp | 
                                                                                Type | 
                                                                        N/A Natural Gas | 
                                                                                Style | 
                                                                        N/A State Titan® Large Volume | 
                                                                                Size | 
                                                                        N/A C | 
                                                                                Industry Standards | 
                                                                        N/A ASHRAE/IESNA 90.1 ASME Certified CSA® Certified UL® Listed | 
                                                                                Recovery at 80 ºF Temperature Rise | 
                                                                        N/A 970 gal/h | 
                                                                                Recovery at 100 ºF Temperature Rise | 
                                                                        N/A 776 gal/h | 
                                                                                Recovery at 140 ºF Temperature Rise | 
                                                                        N/A 554 gal/h | 
                                                                                Features | 
                                                                        
                                                                                    
                                                                                        N/A
                                                                                          
  | 
                                                    
                                                                                Other Features | 
                                                                        
                                                                                    
                                                                                        N/A
                                                                                          
  | 
                                                    
                                                                                Note | 
                                                                        
                                                                                    
                                                                                        N/A
                                                                                          Certified Minimum Installation Clearances to Combustibles:
 Minimum gas supply pressure: 7 Inches W.C. Maximum gas supply pressure: 13 Inches W.C. TPG models are Category I appliances (Fan Assisted) and require a negative draft. These units should only be commonly vented with other Category I negative draft appliances per the latest addition of the National Fuel Gas Code. An approved/listed Type "B" venting material is recommended. A negative draft of -0.02" to -0.07 is required in the vent.  |