Catalog
Cyclone® MXi Modulating
Modulating burner advances the cyclone® to higher levels of efficiency.
Modulating burner advances the cyclone® to higher levels of efficiency.
Unit of Measure
Specifications
|
Maximum Recovery (ºF)
|
Maximum Recovery (ºC)
|
Dimensions
|
Electrical Characteristics
|
3" Vent Pipe
|
4" Vent Pipe
|
Optional Kits
|
Features
|
Testing and Certifications
|
Warranty
Specifications
Manufacturer |
N/A A. O. Smith® |
Type |
N/A Liquid Propane Gas Natural Gas |
Input Power |
N/A 199900 BTU/hr58 kW |
Thermal Efficiency |
N/A 97 % |
Approximate Capacity |
N/A 100 U.S. gal379 L100 gal |
Size of Gas Connection |
N/A 3/4 in. NPT |
Standard Shipping Weight |
N/A 523 lb237 kg |
ASME Shipping Weight |
N/A 553 lb251 kg |
Minimum Gas Supply Pressure |
N/A For Liquid Propane Gas: 2.12 kPaFor Natural Gas: 1.10 kPaFor Liquid Propane Gas: 8.5 inWcFor Natural Gas: 4.4 inWc |
Maximum Gas Supply Pressure |
N/A 14 inWc3.49 kPa |
Number of Installed Elbows |
N/A 1 2 3 4 5 6 |
Industry Standards |
N/A ANSI Z-21.10.3 - CSA 4.3 ASHRAE/IESNA 90.1 ASME Certified ASME Optional NSF |
Note |
N/A Recovery capacities are based on AHRI rated thermal efficiencies. |
Maximum Recovery (ºF)
Recovery at 30 ºF Temperature Rise |
N/A 783 gal/h |
Recovery at 40 ºF Temperature Rise |
N/A 588 gal/h |
Recovery at 50 ºF Temperature Rise |
N/A 470 gal/h |
Recovery at 60 ºF Temperature Rise |
N/A 392 gal/h |
Recovery at 70 ºF Temperature Rise |
N/A 336 gal/h |
Recovery at 80 ºF Temperature Rise |
N/A 294 gal/h |
Recovery at 90 ºF Temperature Rise |
N/A 261 gal/h |
Recovery at 100 ºF Temperature Rise |
N/A 235 gal/h |
Recovery at 110 ºF Temperature Rise |
N/A 214 gal/h |
Recovery at 120 ºF Temperature Rise |
N/A 196 gal/h |
Recovery at 130 ºF Temperature Rise |
N/A 181 gal/h |
Recovery at 140 ºF Temperature Rise |
N/A 168 gal/h |
Maximum Recovery (ºC)
Recovery at 17 ºC Temperature Rise |
N/A 2965 L/h |
Recovery at 22 ºC Temperature Rise |
N/A 2224 L/h |
Recovery at 28 ºC Temperature Rise |
N/A 1779 L/h |
Recovery at 33 ºC Temperature Rise |
N/A 1483 L/h |
Recovery at 39 ºC Temperature Rise |
N/A 1271 L/h |
Recovery at 44 ºC Temperature Rise |
N/A 1112 L/h |
Recovery at 50 ºC Temperature Rise |
N/A 988 L/h |
Recovery at 56 ºC Temperature Rise |
N/A 890 L/h |
Recovery at 61 ºC Temperature Rise |
N/A 809 L/h |
Recovery at 67 ºC Temperature Rise |
N/A 741 L/h |
Recovery at 72 ºC Temperature Rise |
N/A 684 L/h |
Recovery at 78 ºC Temperature Rise |
N/A 635 L/h |
Dimensions
3" Vent Pipe
One 90º Elbows for Maximum 3" Vent Pipe |
N/A 45 ft13.7 m |
Two 90º Elbows for Maximum 3" Vent Pipe |
N/A 40 ft12.2 m |
Three 90º Elbows for Maximum 3" Vent Pipe |
N/A 35 ft10.7 m |
Four 90º Elbows for Maximum 3" Vent Pipe |
N/A 30 ft9.1 m |
4" Vent Pipe
One 90º Elbows for Maximum 4" Vent Pipe |
N/A 115 ft35 m |
Two 90º Elbows for Maximum 4" Vent Pipe |
N/A 110 ft33.5 m |
Three 90º Elbows for Maximum 4" Vent Pipe |
N/A 105 ft32 m |
Four 90º Elbows for Maximum 4" Vent Pipe |
N/A 100 ft30.5 m |
Five 90º Elbows for Maximum 4" Vent Pipe |
N/A 95 ft29 m |
Six 90º Elbows for Maximum 4" Vent Pipe |
N/A 90 ft27.4 m |
Optional Kits
Optional Kits |
N/A
|
Features
Features |
N/A
The full line of A. O. Smith Cyclone® Mxi condensing water heaters has been designed to provide years of dependable service and feature industry leading technology. Models are available from 120000 to 500000 Btu/h and all deliver thermal efficiencies of 95 % and higher. The unique helical coil heat exchanger limits weld joints for optimal service life while maximizing heat transfer. Cyclone is the industry leader in high efficiency commercial water heating with over a quarter million Cyclone®s sold since 1996. The current Mxi modulating models adjust firing rate to the specific demand further increasing efficiency and money savings. Intelligent Control System with Lcd Display
|
Testing and Certifications
Testing and Certifications |
N/A
Codes and Standards
|