Catalog
The Ultra Force™ SUF product line is the most efficient State commercial water heater line ever built. With a storage tank of up to 130 gallons, high BTU input and up to 96% thermal efficiency, these models deliver more hot water for every energy dollar. A single Ultra Force™ unit is an ideal energy-saving choice for restaurants and other mid-sized commercial applications. Multiple Ultra Force™ water heaters can be manifolded together to meet the demands of large commercial and industrial applications.
Unit of Measure
Specifications
|
Maximum Recovery
|
Dimensions
|
3" Vent Pipe
|
4" Vent Pipe
|
General Information
|
Features
|
Other Features
|
Testing and Certifications
|
Warranty
|
Note
Specifications
Manufacturer |
N/A State® |
Standard Type |
N/A Non-ASME |
Input Power |
N/A 150000 BTU/hr44 kW |
Thermal Efficiency |
N/A 95 % |
Capacity |
N/A 100 U.S. gal379 L |
Standard Approximate Shipping Weight |
N/A 555 lb252 kg |
ASME Approximate Shipping Weight |
N/A 595 lb270 kg |
Minimum Supply Natural Gas Line Size (N.P.T.) |
N/A 3/4 in |
Minimum Supply Propane Gas Line Size (N.P.T.) |
N/A 3/4 in |
Water Connection |
N/A 1-1/2 in |
Type |
N/A Liquid Propane Gas Natural Gas |
Style |
N/A Ultra Force™ |
Size |
N/A C |
Industry Standards |
N/A AHRI Certified® ASHRAE/IESNA 90.1 ASME Certified CSA® Certified Energy Star UL® Listed |
Maximum Recovery
Recovery at 30 ºF Temperature Rise |
N/A 576 gal/h |
Recovery at 17 ºC Temperature Rise |
N/A 2179 L/h |
Recovery at 40 ºF Temperature Rise |
N/A 432 gal/h |
Recovery at 22 ºC Temperature Rise |
N/A 1635 L/h |
Recovery at 50 ºF Temperature Rise |
N/A 345 gal/h |
Recovery at 28 ºC Temperature Rise |
N/A 1308 L/h |
Recovery at 60 ºF Temperature Rise |
N/A 288 gal/h |
Recovery at 33 ºC Temperature Rise |
N/A 1090 L/h |
Recovery at 70 ºF Temperature Rise |
N/A 247 gal/h |
Recovery at 39 ºC Temperature Rise |
N/A 934 L/h |
Recovery at 80 ºF Temperature Rise |
N/A 216 gal/h |
Recovery at 44 ºC Temperature Rise |
N/A 817 L/h |
Recovery at 90 ºF Temperature Rise |
N/A 192 gal/h |
Recovery at 50 ºC Temperature Rise |
N/A 726 L/h |
Recovery at 100 ºF Temperature Rise |
N/A 173 gal/h |
Recovery at 56 ºC Temperature Rise |
N/A 654 L/h |
Recovery at 110 ºF Temperature Rise |
N/A 157 gal/h |
Recovery at 61 ºC Temperature Rise |
N/A 594 L/h |
Recovery at 120 ºF Temperature Rise |
N/A 144 gal/h |
Recovery at 67 ºC Temperature Rise |
N/A 545 L/h |
Recovery at 130 ºF Temperature Rise |
N/A 133 gal/h |
Recovery at 72 ºC Temperature Rise |
N/A 503 L/h |
Recovery at 140 ºF Temperature Rise |
N/A 123 gal/h |
Recovery at 78 ºC Temperature Rise |
N/A 467 L/h |
3" Vent Pipe
One 90º Elbows for Maximum 3" Vent Pipe |
N/A 45 ft13.7 m |
Two 90º Elbows for Maximum 3" Vent Pipe |
N/A 40 ft12.2 m |
Three 90º Elbows for Maximum 3" Vent Pipe |
N/A 35 ft10.7 m |
Four 90º Elbows for Maximum 3" Vent Pipe |
N/A 30 ft9.1 m |
4" Vent Pipe
One 90º Elbows for Maximum 4" Vent Pipe |
N/A 115 ft35 m |
Two 90º Elbows for Maximum 4" Vent Pipe |
N/A 110 ft33.5 m |
Three 90º Elbows for Maximum 4" Vent Pipe |
N/A 105 ft32 m |
Four 90º Elbows for Maximum 4" Vent Pipe |
N/A 100 ft30.5 m |
Five 90º Elbows for Maximum 4" Vent Pipe |
N/A 95 ft29 m |
Six 90º Elbows for Maximum 4" Vent Pipe |
N/A 90 ft27.4 m |
General Information
General Information |
N/A
Installation Considerations
|
Features
Features |
N/A
Down-Fired Low NOx Power Burner Design
|
Other Features
Other Features |
N/A
Commercial Grade Glasslined Tank & Heat Exchanger for Long-Term Protection Against Corrosion
|
Testing and Certifications
Testing and Certifications |
N/A
ASME Construction
CSA® Certified and ASME Rated T&P Relief Valve All models are ENERGY STAR® Qualified |
Note
Note |
N/A
Recovery capacities are based on heater performance at 95% and 96% thermal efficiency. Maximum gas supply pressure: 10.5" W.C. natural gas 14" W.C. propane. Electrical requirements: 120/60 Hz VAC, Blower 2.2 Amps FL, Igniter 4.0 Amps. Minimum clearance to remove top cover. Additional clearances recommended in case service is needed. Maximum number of 90º elbows allowed for the vent (exhaust) pipe is four (4) when installing 3 inch pipe and six (6) when installing 4 inch pipe. Maximum number of 90º elbows allowed for intake air pipe is four (4) when installing 3 inch pipe and six (6) when installing 4 inch pipe. Two (2) 45º elbows equal one (1) 90º elbow. Center line of water outlet on top of the water heaters is approximately 7 inches from the front edge of the water heater. |