Catalog
		
            TPO - Oil Fired Models: No. 1 or 2 Oil
- Multi-annular fuel containment combustor head
 - Available for firing light fuel oils including diesel
 - Oil ignition transformer
 - Integral 2-stage fuel unit
 - Squirrel cage blower
 - Oil safety valve
 
                    Unit of Measure
                    
               
        
            
                        Specifications
                            |
                        Maximum Recovery
                            |
                        Dimensions
                            |
                        Electrical Characteristics
                            |
                        Features
                            |
                        Other Features
                            |
                        Note
                
            
            Specifications
                                                                                Manufacturer | 
                                                                        N/A State® | 
                                                                                Nominal Storage Capacity | 
                                                                        N/A 300 U.S. gal | 
                                                                                Input Power | 
                                                                        N/A 300000 BTU/hr | 
                                                                                First Hour Rating | 
                                                                        N/A 2.1 gal | 
                                                                                Shipping Weight with Burner | 
                                                                        N/A 2150 lb | 
                                                                                Motor Power | 
                                                                        N/A 1/4 hp | 
                                                                                Type | 
                                                                        N/A Gas | 
                                                                                Style | 
                                                                        N/A State Titan® Power Low NOx | 
                                                                                Size | 
                                                                        N/A C | 
                                                                                Industry Standards | 
                                                                        N/A ASHRAE/IESNA 90.1 ASME Certified CSA® Certified UL® Listed | 
Maximum Recovery
                                                                                Recovery at 80 ºF Temperature Rise | 
                                                                        N/A 364 gal/h | 
                                                                                Recovery at 100 ºF Temperature Rise | 
                                                                        N/A 291 gal/h | 
                                                                                Recovery at 140 ºF Temperature Rise | 
                                                                        N/A 208 gal/h | 
Dimensions
Features
                                                                                Features | 
                                                                        
                                                                                    
                                                                                        N/A
                                                                                          
  | 
                                                    
Other Features
                                                                                Other Features | 
                                                                        
                                                                                    
                                                                                        N/A
                                                                                          
  | 
                                                    
Note
                                                                                Note | 
                                                                        
                                                                                    
                                                                                        N/A
                                                                                          Certified Minimum Installation Clearances to Combustibles:
 State Titan TPO models are Category I appliances (Fan Assisted) and require a negative draft. These units should only be commonly vented with other Category I negative draft appliances per the latest addition of the National Fuel Gas Code. An approved/listed Type "B" venting material is recommended. A negative draft of -0.02" to -0.07 is required in the vent.  | 
                                                    