Print Back
The Ultra Force™ SUF product line is the most efficient State commercial water heater line ever built. With a storage tank of up to 130 gallons, high BTU input and up to 96% thermal efficiency, these models deliver more hot water for every energy dollar. A single Ultra Force™ unit is an ideal energy-saving choice for restaurants and other mid-sized commercial applications. Multiple Ultra Force™ water heaters can be manifolded together to meet the demands of large commercial and industrial applications.
Unit of Measure

Specifications

Manufacturer

N/A State®

Standard Type

N/A Non-ASME

Input Power

N/A 199900 BTU/hr58 kW

Thermal Efficiency

N/A 95 %

Capacity

N/A 100 U.S. gal379 L

Standard Approximate Shipping Weight

N/A 555 lb252 kg

ASME Approximate Shipping Weight

N/A 595 lb270 kg

Minimum Supply Natural Gas Line Size (N.P.T.)

N/A 3/4 in

Minimum Supply Propane Gas Line Size (N.P.T.)

N/A 3/4 in

Water Connection

N/A 1-1/2 in

Type

N/A Liquid Propane Gas Natural Gas

Style

N/A Ultra Force™

Size

N/A C

Industry Standards

N/A AHRI Certified® ASHRAE/IESNA 90.1 ASME Certified CSA® Certified Energy Star UL® Listed

Maximum Recovery

Recovery at 30 ºF Temperature Rise

N/A 767 gal/h

Recovery at 17 ºC Temperature Rise

N/A 2904 L/h

Recovery at 40 ºF Temperature Rise

N/A 575 gal/h

Recovery at 22 ºC Temperature Rise

N/A 2178 L/h

Recovery at 50 ºF Temperature Rise

N/A 460 gal/h

Recovery at 28 ºC Temperature Rise

N/A 1743 L/h

Recovery at 60 ºF Temperature Rise

N/A 384 gal/h

Recovery at 33 ºC Temperature Rise

N/A 1452 L/h

Recovery at 70 ºF Temperature Rise

N/A 329 gal/h

Recovery at 39 ºC Temperature Rise

N/A 1245 L/h

Recovery at 80 ºF Temperature Rise

N/A 288 gal/h

Recovery at 44 ºC Temperature Rise

N/A 1089 L/h

Recovery at 90 ºF Temperature Rise

N/A 256 gal/h

Recovery at 50 ºC Temperature Rise

N/A 968 L/h

Recovery at 100 ºF Temperature Rise

N/A 230 gal/h

Recovery at 56 ºC Temperature Rise

N/A 871 L/h

Recovery at 110 ºF Temperature Rise

N/A 209 gal/h

Recovery at 61 ºC Temperature Rise

N/A 792 L/h

Recovery at 120 ºF Temperature Rise

N/A 192 gal/h

Recovery at 67 ºC Temperature Rise

N/A 726 L/h

Recovery at 130 ºF Temperature Rise

N/A 177 gal/h

Recovery at 72 ºC Temperature Rise

N/A 670 L/h

Recovery at 140 ºF Temperature Rise

N/A 164 gal/h

Recovery at 78 ºC Temperature Rise

N/A 622 L/h

Dimensions

Schematic

N/A

Dimension A

N/A 3 in7.62 cm

Dimension B

N/A 27.75 in70.5 cm

Dimension C

N/A 6.3 in16 cm

Dimension D

N/A 55.5 in141 cm

Dimension E

N/A 75.5 in191.8 cm

Dimension F

N/A 75.5 in191.8 cm

Dimension G

N/A 11 in27.9 cm

Dimension H

N/A 63 in160 cm

Dimension I

N/A 69 in175.3 cm

3" Vent Pipe

One 90º Elbows for Maximum 3" Vent Pipe

N/A 45 ft13.7 m

Two 90º Elbows for Maximum 3" Vent Pipe

N/A 40 ft12.2 m

Three 90º Elbows for Maximum 3" Vent Pipe

N/A 35 ft10.7 m

Four 90º Elbows for Maximum 3" Vent Pipe

N/A 30 ft9.1 m

4" Vent Pipe

One 90º Elbows for Maximum 4" Vent Pipe

N/A 115 ft35 m

Two 90º Elbows for Maximum 4" Vent Pipe

N/A 110 ft33.5 m

Three 90º Elbows for Maximum 4" Vent Pipe

N/A 105 ft32 m

Four 90º Elbows for Maximum 4" Vent Pipe

N/A 100 ft30.5 m

Five 90º Elbows for Maximum 4" Vent Pipe

N/A 95 ft29 m

Six 90º Elbows for Maximum 4" Vent Pipe

N/A 90 ft27.4 m

General Information

General Information

N/A Installation Considerations
  1. Condensate Drain - This is a fully condensing water heater and should be located near a drain to permit proper disposal of condensate.
  2. Vent Termination - Exhaust gases of this water heater are less than 140 ºF. In cold climates, water vapor in flue gases will condense into a cloud of vapor where the vent exits the building. This vapor can gradually discolor exterior building surfaces. Vent termination should be located where this vapor cloud and potential discoloration are not a concern. Extending the vent termination up to 6" from the wall helps vapor from being trapped along a building's face. To avoid this problem, the vent can be terminated on the roof. Always locate vent termination above the maximum snowline, and do not locate vent termination above a walkway.
  3. Air Intake - In cold climates, air intake should be located at least four feet from the vent termination of the water heater and any other appliance vents that discharge moisture-laden air (such as clothes dryers). This will help prevent freeze-over of the intake screen required to prevent foreign objects from entering the intake pipe. Air intake should be located above the maximum snowline.
  4. Blockage Sensors - The water heater is equipped with sensors to shut it down if blockage of vent or air intake occurs. The water heater control system will display detailed diagnostic information on the LCD screen to help service technicians quickly locate and correct the problem.
  5. Noise - Vent terminal should be located away from bedroom windows or other areas where blower noise will be objectionable. Avoid venting into corners or confined areas, which will amplify sound. Anchoring intake or vent pipe walls or ceilings can cause noise to be transmitted to living areas, and isolation mounts should be used where anchoring is required.
  6. Optional Concentric Vent Kit - Helps to minimize unsightly wall/roof penetrations.
    SUF 60 120NE - SUF 130 300NEA vent kit p/n 9006328005
    SUF 130-400-500 NEA vent kit p/n 9006144005

Features

Features

N/A Down-Fired Low NOx Power Burner Design
  • Top-mounted radial burner design ensures optimum combustion efficiency.
Fully Submerged, Spiral-Shaped Condensing Heat Exchanger
  • Spiral shaped heat exchanger coils keeps hot flue gases swirling through the heat exchanger maximizing heat transfer and efficiency.
  • Spiral shaped heat exchanger reduces the accumulation of lime scale; maintains higher efficiency performance over time.
Standard Power Vent or Power Direct Vent Flexibility
  • Vertical or sidewall power-venting.
  • Vertical or sidewall powered-direct vent draws all combustion air from outside the building.
  • Vents using inexpensive PVC, ABS or CPVC pipe. Canadian installations require ULC S636 listed PVC or CPVC pipe for intake and exhaust.
  • Air intake and vent runs can be up to 120 equivalent feet.
Space-Saving Design, with Zero Clearance to Combustibles
  • Approved for installation on combustible flooring.
All Controls Including Gas Valve and Combustion Air Blower Located on Top
  • Provides easy access during installation and service.
  • Protects against high water damage.
  • Protected from dirt and incidental damage.
Advanced Electronic Control System
  • Microprocessor controls all water heater functions including ignition and temperature regulation.
  • Precise temperature control adjustable from 90 ºF to 180 ºF.
  • Large LCD display provides detailed operational and diagnostic information in plain English for ease of operation and service.
  • Ultra Force water heaters are iCOMM™ compatible and can be monitored from remote locations. Call 1.888.WATER02 for more information.
Powered Anodes (Standard on All Models).
  • Provide long-lasting tank protection.
  • Non sacrificial anodes never need replacing unless damaged.

Other Features

Other Features

N/A Commercial Grade Glasslined Tank & Heat Exchanger for Long-Term Protection Against Corrosion
  • Heat exchanger glasslined on both water and vent sides to protect against corrosive flue gases and condensate inside the coil
Handhole Cleanout
  • For easy inspection and cleaning
Compliance
  • Meets the Thermal Efficiency and Standby Loss Requirements of the U. S. Department of Energy and Current Edition of ASHRAE/IESNA 90.1
  • Complies with SCAQMD Rule 1146.2 and other air quality management districts with similar requirements for NOx emissions
  • The 120-250K BTU models are design-certified by CSA® International, according to ANSI Z21.10.3 - CSA® 4.3 Standards governing storage-type water heaters
  • The 300-500K BTU models are design-certified by Underwriter's Laboratories (UL), Inc., according to ANSI Z21.10.3-4.3 CSA® Standards governing storage-type water heaters
  • Design-certified by Underwriter's Laboratories (UL), Inc., to NSF Standard 5

Testing and Certifications

Testing and Certifications

N/A ASME Construction
  • Optional on all models
Maximum Hydrostatic Working Pressure: 160 psi

CSA® Certified and ASME Rated T&P Relief Valve

All models are ENERGY STAR® Qualified

Warranty

Warranty

N/A
  • 3-Year Limited Tank Warranty.

Note

Note

N/A Recovery capacities are based on heater performance at 95% and 96% thermal efficiency.

Maximum gas supply pressure: 10.5" W.C. natural gas 14" W.C. propane.

Electrical requirements: 120/60 Hz VAC, Blower 2.2 Amps FL, Igniter 4.0 Amps.

Minimum clearance to remove top cover. Additional clearances recommended in case service is needed.

Maximum number of 90º elbows allowed for the vent (exhaust) pipe is four (4) when installing 3 inch pipe and six (6) when installing 4 inch pipe. Maximum number of 90º elbows allowed for intake air pipe is four (4) when installing 3 inch pipe and six (6) when installing 4 inch pipe. Two (2) 45º elbows equal one (1) 90º elbow.

Center line of water outlet on top of the water heaters is approximately 7 inches from the front edge of the water heater.