Manufacturer |
N/A Bradford White® |
Capacity |
N/A 50 U.S. gal42 Imp. gal189 L |
Approximate Shipping Weight |
N/A 137 lb62 kg |
Voltage |
N/A 208 V240 V277 V380 V415 V480 V |
Phase |
N/A Single Three |
Input Power |
N/A 6 kW |
Each Element Power |
N/A 2000 W |
Kit Part Numbers for 208 V |
N/A 265-43942-13 |
Kit Part Numbers for 240 V |
N/A 265-43942-07 |
Kit Part Numbers for 480 V |
N/A 265-43942-01 |
Test Pressure |
N/A 300 psi2068 kPa |
Working Pressure |
N/A 150 psi1034 kPa |
Style |
N/A Triflex Medium-Duty |
Size |
N/A C |
Type |
N/A Electric |
Industry Standards |
N/A ASHRAE 90.1b (Current Standards) C.E.C. Listed CSA® Certified |
Recovery at 40 ºF Temperature Rise |
N/A 62 gal/h |
Recovery at 100 ºF Temperature Rise |
N/A 74 U.S. gal/h62 Imp. gal/h25 gal/h |
Recovery at 140 ºF Temperature Rise |
N/A 18 gal/h |
Recovery at 56 ºC Temperature Rise |
N/A 280 L/h |
Full Load Current Single Phase 208 V |
N/A 28.8 A |
Full Load Current Three Phase 208 V |
N/A 16.7 A |
Full Load Current Single Phase 240 V |
N/A 25 A |
Full Load Current Three Phase 240 V |
N/A 14.4 A |
Full Load Current Single Phase 277 V |
N/A 21.7 A |
Full Load Current Single Phase 380 V |
N/A 9.1 A |
Full Load Current Single Phase 415 V |
N/A 8.3 A |
Full Load Current Single Phase 480 V |
N/A 12.5 A |
Full Load Current Three Phase 480 V |
N/A 7.2 A |
Features |
N/A
|
General Information |
N/A
All models ETL listed. All potable water connections are 1-1/4" NPT (25 mm) on 8" (203 mm) centers. All electrical connections are 3/4" (19 mm) NPT. All models certified at 300 psi test pressure (2068 kPa) and 150 psi working pressure (1034 kPa). Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement. |