Manufacturer |
N/A State® |
Standard Type |
N/A Non-ASME |
Input Power |
N/A 120000 BTU/hr35 kW |
Thermal Efficiency |
N/A 95 % |
Capacity |
N/A 60 U.S. gal227 L |
Standard Approximate Shipping Weight |
N/A 460 lb208 kg |
ASME Approximate Shipping Weight |
N/A 490 lb222 kg |
Minimum Supply Natural Gas Line Size (N.P.T.) |
N/A 1/2 in |
Minimum Supply Propane Gas Line Size (N.P.T.) |
N/A 1/2 in |
Water Connection |
N/A 1-1/2 in |
Type |
N/A Liquid Propane Gas Natural Gas |
Style |
N/A Ultra Force™ |
Size |
N/A C |
Industry Standards |
N/A AHRI Certified® ASHRAE/IESNA 90.1 ASME Certified CSA® Certified Energy Star UL® Listed |
Recovery at 30 ºF Temperature Rise |
N/A 461 gal/h |
Recovery at 17 ºC Temperature Rise |
N/A 1744 L/h |
Recovery at 40 ºF Temperature Rise |
N/A 345 gal/h |
Recovery at 22 ºC Temperature Rise |
N/A 1308 L/h |
Recovery at 50 ºF Temperature Rise |
N/A 276 gal/h |
Recovery at 28 ºC Temperature Rise |
N/A 1046 L/h |
Recovery at 60 ºF Temperature Rise |
N/A 230 gal/h |
Recovery at 33 ºC Temperature Rise |
N/A 872 L/h |
Recovery at 70 ºF Temperature Rise |
N/A 197 gal/h |
Recovery at 39 ºC Temperature Rise |
N/A 747 L/h |
Recovery at 80 ºF Temperature Rise |
N/A 173 gal/h |
Recovery at 44 ºC Temperature Rise |
N/A 654 L/h |
Recovery at 90 ºF Temperature Rise |
N/A 154 gal/h |
Recovery at 50 ºC Temperature Rise |
N/A 581 L/h |
Recovery at 100 ºF Temperature Rise |
N/A 138 gal/h |
Recovery at 56 ºC Temperature Rise |
N/A 523 L/h |
Recovery at 110 ºF Temperature Rise |
N/A 126 gal/h |
Recovery at 61 ºC Temperature Rise |
N/A 476 L/h |
Recovery at 120 ºF Temperature Rise |
N/A 115 gal/h |
Recovery at 67 ºC Temperature Rise |
N/A 436 L/h |
Recovery at 130 ºF Temperature Rise |
N/A 106 gal/h |
Recovery at 72 ºC Temperature Rise |
N/A 402 L/h |
Recovery at 140 ºF Temperature Rise |
N/A 99 gal/h |
Recovery at 78 ºC Temperature Rise |
N/A 374 L/h |
One 90º Elbows for Maximum 3" Vent Pipe |
N/A 45 ft13.7 m |
Two 90º Elbows for Maximum 3" Vent Pipe |
N/A 40 ft12.2 m |
Three 90º Elbows for Maximum 3" Vent Pipe |
N/A 35 ft10.7 m |
Four 90º Elbows for Maximum 3" Vent Pipe |
N/A 30 ft9.1 m |
One 90º Elbows for Maximum 4" Vent Pipe |
N/A 115 ft35 m |
Two 90º Elbows for Maximum 4" Vent Pipe |
N/A 110 ft33.5 m |
Three 90º Elbows for Maximum 4" Vent Pipe |
N/A 105 ft32 m |
Four 90º Elbows for Maximum 4" Vent Pipe |
N/A 100 ft30.5 m |
Five 90º Elbows for Maximum 4" Vent Pipe |
N/A 95 ft29 m |
Six 90º Elbows for Maximum 4" Vent Pipe |
N/A 90 ft27.4 m |
General Information |
N/A
Installation Considerations
|
Features |
N/A
Down-Fired Low NOx Power Burner Design
|
Other Features |
N/A
Commercial Grade Glasslined Tank & Heat Exchanger for Long-Term Protection Against Corrosion
|
Testing and Certifications |
N/A
ASME Construction
CSA® Certified and ASME Rated T&P Relief Valve All models are ENERGY STAR® Qualified |
Note |
N/A
Recovery capacities are based on heater performance at 95% and 96% thermal efficiency. Maximum gas supply pressure: 10.5" W.C. natural gas 14" W.C. propane. Electrical requirements: 120/60 Hz VAC, Blower 2.2 Amps FL, Igniter 4.0 Amps. Minimum clearance to remove top cover. Additional clearances recommended in case service is needed. Maximum number of 90º elbows allowed for the vent (exhaust) pipe is four (4) when installing 3 inch pipe and six (6) when installing 4 inch pipe. Maximum number of 90º elbows allowed for intake air pipe is four (4) when installing 3 inch pipe and six (6) when installing 4 inch pipe. Two (2) 45º elbows equal one (1) 90º elbow. Center line of water outlet on top of the water heaters is approximately 7 inches from the front edge of the water heater. |