Print Back
Unit of Measure

Specifications

Manufacturer

N/A Bradford White®

Capacity

N/A 100 U.S. gal83 Imp. gal379 L

Input Power

N/A 150000 BTU/hr43.9 kW

Standard Approximate Shipping Weight

N/A 735 lb333 kg

Style

N/A Power Direct Independent Vent

Size

N/A C

Type

N/A Natural Gas

Test Pressure

N/A 300 psi2068 kPa

Working Pressure

N/A 150 psi1034 kPa

Industry Standards

N/A AHRI Certified® ANSI Standards Z-21.10.3 ASME Certified CSA® Certified NSF

Maximum Recovery

Recovery at 40 ºF Degree Rise

N/A 364 gal/h

Recovery at 4.4 ºC Degree Rise

N/A 1378 L/h

Recovery at 100 ºF Degree Rise

N/A 145 gal/h

Recovery at 56 ºC Degree Rise

N/A 549 L/h

Recovery at 140 ºF Degree Rise

N/A 104 gal/h

Recovery at 60 ºC Degree Rise

N/A 394 L/h

Dimensions

Schematic

N/A
Schematic Drawing for Commercial Power Direct Vent Independent Vent Energy Saver Gas Water Heaters

Floor to Top of Heater A

N/A 72-7/8 in1832 mm

Jacket Diameter B

N/A 28-1/4 in718 mm

Vent Size C

N/A 3 in76 mm

Floor to Gas Connection D

N/A 17-3/8 in438 mm

Front Cold Water Connection E

N/A 20-3/4 in525 mm

Front Hot Water Connection F

N/A 60-3/8 in1532 mm

Floor to Top Water Connection G

N/A 74-3/4 in1883 mm

Floor to Vent Connection H

N/A 77-7/8 in1961 mm

Depth K

N/A 43-7/8 in1117 mm

3" Vent Pipe

Maximum Intake Length for 3" Vent Pipe

N/A 45 ft

Maximum Exhaust Length for 3" Vent Pipe

N/A 45 ft

4" Vent Pipe

Maximum Intake Length for 4" Vent Pipe

N/A 60 ft

Maximum Exhaust Length for 4" Vent Pipe

N/A 60 ft

General Information

General Information

N/A All gas water heaters are certified at 300 psi test pressure (2068 kPa) and 150 psi working pressure (1034 kPa). All models are design certified by CSA® International (formerly AGA/CGA), ANSI standard Z-21.10.3, for up to 180 ºF (82 ºC) application as an Automatic Storage Heater, and an Automatic Circulating Tank Heater. As an Automatic Storage Heater, all models are complete, self-contained water heating systems. It needs no separate storage tank, pump, wiring or elaborate piping network. When equipped with a mixing valve, it will supply 180 ºF (82 ºC) sanitizing and lower temperature general purpose hot water simultaneously. These models can be used either as a single unit or in multiples connected in series or parallel (recommended).

Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.

Features

Features

N/A The Power Direct Vent Independent Vent Models feature:
  • ICON HD™ - Intelligent proven design combines temperature control, diagnostic codes, and system ignition functions into a single control board with a digital LCD display. Control panel cover tilts down for ease of wiring and service.
  • Honeywell Integrated Control - Intelligent proven design combines temperature control, diagnostic codes, and system ignition function into a single control board with a digital LCD display. Control panel cover tilts down for ease of wiring and service.
  • Operation Mode - Two different digitally displayed operation modes have the capability of adjusting the temperature setting up to 180 ºF (82ºC), and adjusting the degree setting (ºF to ºC, or ºC to ºF).
  • Service Mode - Eight different digitally displayed service modes can be easily cycled through by pressing the select button. There is the capability of adjusting the temperature setting up to 180 ºF (82 ºC), adjusting the degree setting (ºF to ºC, or ºC to ºF), locking the maximum temperature setting that can be adjusted in operation mode, displaying the average water temperature (if water heater has two sensors), displaying the upper temperature sensor, displaying the lower temperature sensor, displaying the flame current of the pilot flame, and displaying diagnostic codes.
  • Automatic Blower Motor - Induced draft for direct venting.
  • Electronic Ignition - High voltage, low current electricity is sent to the pilot electrode initiating a spark to ignite the pilot gas. This results in savings of pilot gas during stand-by periods because the pilot flame only operates when there's a call for heat.
  • Factory Installed Hydrojet® 2™ Sediment Reduction System - Cold water inlet sediment reducing device helps prevent sediment build up in the tank.
  • Independent Vent System - This allows combustible air to enter from the outside through one pipe and exhausts the products of combustion through another pipe (max. equivalent vent length for each pipe on reverse side).
  • Vitraglas® Lining - Bradford White tanks are lined with a exclusively engineered enamel formula that provides superior protection from the highly corrosive effects of hot water. This formula (Vitraglas®) is fused to the steel surface by firing at a temperature of over 1600 ºF (871 ºC).
  • E.C.O. - An automatic re-set Energy Cut Off (E.C.O) shuts off all gas in event of an overheat condition. This automatically re-sets when operation conditions are back to normal.
  • Non-CFC Foam Insulation - Covers the sides and top of tank, reducing the amount of heat loss. This results in less energy consumption, improved operation efficiencies and jacket rigidity.
  • Water Connections - Multiple water connection locations allow for greater installation flexibility. 1 1/2" NPT top and front, 2" NPT rear factory installed true dielectric fittings extend water heater life and eases installation.
  • Protective Magnesium Anode Rods - Provide added protection against corrosion for long trouble-free service.
  • Hand Hole Cleanout - Allows inspection of tank interior and removal of sediment deposits.
  • Sanitizing Capability - Temperature setting up to 180 ºF (82 ºC).
  • NSF Construction Available.
  • ASME Construction Available on 250,000 BTU model (73.2 kW).
  • Low NOx Construction Available.
  • T & P Relief Valve - Installed.
  • Brass Drain Valve - Tamper proof.
  • Design Certified by CSA International (Formerly AGA and CGA).

Warranty

Warranty

N/A
  • 5-Year Limited Warranty - On Inner Glass-Lined Tank.
  • 1-Year Limited Warranty - On all Other Component Parts.

Note

Note

N/A Meet or exceed ASHRAE 90.1b (current standard) C.E.C. Listed 80% Recovery Efficiency.