Print Back
Designed for use as a recovery heater having its own storage tank or booster for supplying sanitizing rinse water for dishwashing.
Unit of Measure

Specifications

Manufacturer

A. O. Smith®

Input Power

13.5 kW46075 BTU/hr

Number of Elements

3

Element Power

4500 W

Tank Capacity

119 gal450 L

Equipment Grade

Commercial

Inlet/Outlet (NPT)

1-1/4 in3.2 cm

Approximate Shipping Weight

390 lb117 kg

Heating Source

Electric

Industry Standards

ASHRAE/IESNA 90.1 ASME Certified

Electrical Characteristics

Full Load Current Single Phase 208 V

64.9 A

Full Load Current Single Phase 240 V

56.3 A

Full Load Current Single Phase 277 V

48.7 A

Full Load Current Single Phase 480 V

28.1 A

Full Load Current Three Phase 208 V

37.5 A

Full Load Current Three Phase 240 V

32.5 A

Full Load Current Three Phase 480 V

16.2 A

Standard Voltage

208 V240 V480 V

Phase

Single Three

Dimensions

Schematic


Schematic Drawing for Gold Xi™ DVE Series Commercial Electric Water Heaters

Dimension A

62-1/4 in158.1 cm

Dimension B

29-1/2 in75 cm

Dimension C

35 in88.9 cm

Maximum Recovery (ºF)

Recovery at 30 ºF Temperature Rise

184 gal/h

Recovery at 40 ºF Temperature Rise

138 gal/h

Recovery at 50 ºF Temperature Rise

111 gal/h

Recovery at 60 ºF Temperature Rise

92 gal/h

Recovery at 70 ºF Temperature Rise

79 gal/h

Recovery at 80 ºF Temperature Rise

69 gal/h

Recovery at 90 ºF Temperature Rise

62 gal/h

Recovery at 100 ºF Temperature Rise

55 gal/h

Recovery at 110 ºF Temperature Rise

50 gal/h

Recovery at 120 ºF Temperature Rise

46 gal/h

Recovery at 130 ºF Temperature Rise

43 gal/h

Recovery at 140 ºF Temperature Rise

40 gal/h

Maximum Recovery (ºC)

Recovery at 17 ºC Temperature Rise

698 L/h

Recovery at 22 ºC Temperature Rise

523 L/h

Recovery at 28 ºC Temperature Rise

419 L/h

Recovery at 33 ºC Temperature Rise

349 L/h

Recovery at 39 ºC Temperature Rise

299 L/h

Recovery at 45 ºC Temperature Rise

262 L/h

Recovery at 50 ºC Temperature Rise

233 L/h

Recovery at 56 ºC Temperature Rise

209 L/h

Recovery at 61 ºC Temperature Rise

190 L/h

Recovery at 67 ºC Temperature Rise

174 L/h

Recovery at 72 ºC Temperature Rise

161 L/h

Recovery at 78 ºC Temperature Rise

150 L/h

Testing and Certifications

Testing and Certifications

Meets the thermal efficiency and or standby loss requirements of the U.S. Department of Energy and current edition of ASHRAE/ISENA 90.1.

iCOMM™ Compatible.

Options

Options

Manifold Kits with Isolation Valves - Available for multiple installations. Two heaters #9003429205. Three heaters #9003430205. Four heaters #9003431205.

International Voltages - 220, 380, 400, 415, 480, 575, and 600 volts three-phase available with Y connected elements.

Warranty

Warranty

  • 3-Year Limited Tank Warranty.

Note

Note

For Full Load Current Single Phase 277 V:
Elements available in incoloy only.