Print Back
Heavy Duty Immersion Thermostat Commercial Electric - The ITCE models are designed to provide years of reliable operation in commercial applications. Multiple anodes promote longer tank life through even distribution, for protection of the tank interior. Ideal for heavy-duty commercial applications requiring an immersion thermostat, quick recovery and lots of reliable hot water.
Unit of Measure

Specifications

Manufacturer

N/A American® Water Heater Company

Input Power

N/A 12 kW13.5 kW15 kW18 kW24 kW27 kW30 kW36 kW40.5 kW45 kW54 kW6 kW9 kW

Capacity

N/A 50 gal

Water Connection

N/A 1-1/4 in

Approximate Shipping Weight

N/A 265 lb

Maximum Working Pressure

N/A 150 psi

Finish

N/A Baked Enamel

Equipment Grade

N/A Commercial

Industry Standards

N/A ASHRAE 90.1b-1992 ASHRAE/IESNA 90.1-2004 ASME Optional UL® Listed

Maximum Recovery (ºF) 54 kW Input

Recovery at 30 ºF Temperature Rise

N/A 738 gal/h

Recovery at 40 ºF Temperature Rise

N/A 554 gal/h

Recovery at 50 ºF Temperature Rise

N/A 443 gal/h

Recovery at 60 ºF Temperature Rise

N/A 359 gal/h

Recovery at 70 ºF Temperature Rise

N/A 316 gal/h

Recovery at 80 ºF Temperature Rise

N/A 277 gal/h

Recovery at 90 ºF Temperature Rise

N/A 246 gal/h

Recovery at 100 ºF Temperature Rise

N/A 221 gal/h

Recovery at 110 ºF Temperature Rise

N/A 201 gal/h

Recovery at 120 ºF Temperature Rise

N/A 185 gal/h

Recovery at 130 ºF Temperature Rise

N/A 170 gal/h

Recovery at 140 ºF Temperature Rise

N/A 158 gal/h

Electrical Characteristics

Standard Voltage

N/A 208 V240 V277 V480 V

Phase

N/A Single Three

Dimensions

Schematic

N/A
Schematic Drawing for Heavy Duty ITCE31 Series Commercial Electric Water Heaters

Height Top of Heater A

N/A 55-3/4 in

Width B

N/A 21-3/4 in

Depth C

N/A 27 in

Features

Features

N/A
  • Economy Mode Operation - Control system automatically lowers the operating set point by a programmed value during user defined time periods. Helps reduce operating costs during unoccupied or off - peak demand periods.
  • Linear Sequencing - Banks of heating elements (3 elements per bank) are energized according to adjustable (1 to 20º) differential set points for each bank. First bank on is the last bank off. Helps reduce current surge and provides accurate water temperature control.
  • Gold Plated Elements - The ITCE models ship with gold plated elements. These gold elements provide long life and superior scale resistance.
  • Glass-Lined Tank - Three sizes; 50, 80, and 119 gallon capacity. Tank interior is coated with glass specially developed for water heater use. Tanks rated at 150 psi working pressure; tested at 300 psi. Foam insulation reduces costly heat loss. ASME (optional) maximum working pressure is 150 psi.
  • Power Circuit Fusing - Protects elements and contactors from short circuits, overloading or line surges. Meets National Electric Code requirements (fusing required when current draw exceeds 48 amps).
  • Standard Voltages - 208, 240, and 480 V single-phase and three phase delta. Convertible from three-phase to single-phase (in field) and vice versa (except 208/54 KW). 277 V single-phase also available.
  • Terminal Block - Factory installed. Allows for easy service connection to block.
  • Magnetic Contactors - Heavy duty; UL rated 100,000 cycles.

Testing and Certifications

Testing and Certifications

N/A Meets or exceeds the requirements of ASHRAE 90.1b-1992 and ASHRAE/IESNA 90.1-2004.

Other Standard Features

Other Standard Features

N/A
  • Simplified circuitry, color coded for ease of service
  • Hinged control compartment door for quick, easy access
  • Two anode rods for maximum corrosion protection
  • Cabinet has bonderized undercoat with baked enamel finish
  • Top outlet, side inlet and relief valve openings
  • Nipple and brass drain valve
  • CSA® / ASME temperature and pressure relief valve

Options

Options

N/A Manifold Kits with Isolation Valves - Available for multiple installations. Two heaters #9003429205. Three heaters #9003430205. Four heaters #9003431205.

Optional International Voltages - 220, 380, 400, 415, 480, 575, and 600 volts three phase available with Y connected elements.

Warranty

Warranty

N/A
  • 3-Year Limited Tank Warranty / 1-Year Limited Parts Warranty.

Note

Note

N/A Figured at 1 KW (3413 BTU) = 4.1 Gallons at 100 ºF temperature rise.
Optional ASME construction available.

Elements available in incoloy only.
Figured at 1 KW (3413 BTU) = 4.1 Gallons at 100 ºF temperature rise.
Optional ASME construction available.

208 V models may contain three (3) additional elements.
Figured at 1 KW (3413 BTU) = 4.1 Gallons at 100 ºF temperature rise.
Optional ASME construction available.