Manufacturer

State®

Input Power

390000 BTU/hr114 kW

Capacity

85 U.S. gal322 L

Thermal Efficiency

82 %

Minimum Gas Supply Pressure

0.87 kPa

Maximum Gas Supply Pressure

3.48 kPa

Standard Approximate Shipping Weight

850 lb386 kg

ASME Approximate Shipping Weight

900 lb408 kg

Maximum Working Pressure

160 psi

Style

Sandblaster® Ultra Low NOx

Size

C

Type

Natural Gas

Industry Standards

AHRI Certified® ANSI Z-21.10.3 - CSA 4.3 ASHRAE/IESNA 90.1 ASME Certified CSA® 4.3 UL® Listed

Maximum Recovery

Recovery at 36 ºF Temperature Rise

1069 U.S. gal/h

Recovery at 20 ºC Temperature Rise

4046 L/h

Recovery at 40 ºF Temperature Rise

962 U.S. gal/h

Recovery at 22 ºC Temperature Rise

3641 L/h

Recovery at 50 ºF Temperature Rise

769 U.S. gal/h

Recovery at 28 ºC Temperature Rise

2913 L/h

Recovery at 54 ºF Temperature Rise

712 U.S. gal/h

Recovery at 30 ºC Temperature Rise

2697 L/h

Recovery at 60 ºF Temperature Rise

641 U.S. gal/h

Recovery at 33 ºC Temperature Rise

2427 L/h

Recovery at 70 ºF Temperature Rise

550 U.S. gal/h

Recovery at 39 ºC Temperature Rise

2081 L/h

Recovery at 72 ºF Temperature Rise

534 U.S. gal/h

Recovery at 40 ºC Temperature Rise

2023 L/h

Recovery at 80 ºF Temperature Rise

481 U.S. gal/h

Recovery at 44 ºC Temperature Rise

1820 L/h

Recovery at 90 ºF Temperature Rise

427 U.S. gal/h

Recovery at 50 ºC Temperature Rise

1618 L/h

Recovery at 100 ºF Temperature Rise

385 U.S. gal/h

Recovery at 56 ºC Temperature Rise

1456 L/h

Recovery at 108 ºF Temperature Rise

356 U.S. gal/h

Recovery at 60 ºC Temperature Rise

1349 L/h

Recovery at 110 ºF Temperature Rise

350 U.S. gal/h

Recovery at 61 ºC Temperature Rise

1324 L/h

Recovery at 120 ºF Temperature Rise

321 U.S. gal/h

Recovery at 67 ºC Temperature Rise

1214 L/h

Recovery at 126 ºF Temperature Rise

305 U.S. gal/h

Recovery at 70 ºC Temperature Rise

1156 L/h

Recovery at 130 ºF Temperature Rise

296 U.S. gal/h

Recovery at 72 ºC Temperature Rise

1120 L/h

Recovery at 140 ºF Temperature Rise

275 U.S. gal/h

Recovery at 78 ºC Temperature Rise

1040 L/h

Dimensions

Schematic


Schematic Drawing for Sandblaster® Ultra-Low NOx Commercial Gas Tank-type Water Heaters (SBL85 275N (A))

Dimension A

76 in193 mm

Dimension B

16-1/4 in41.2 mm

Dimension C

78-1/4 in198.8 mm

Dimension D

65-3/4 in167 mm

Dimension E

25-3/4 in65.4 mm

Dimension F

21 in53.3 mm

Dimension G

3/4 in. NPT

Dimension H

66-1/4 in168.3 mm

Dimension I

6 in15.2 mm

Dimension J

27-3/4 in70.5 mm

Dimension K

1-1/2 in. NPT

Dimension L

1-1/2 in. NPT

Dimension M

41 in104 mm

Electrical Characteristics

Minimum Water Connection

3.5 in

Maximum Water Connection

14 in

Voltage

120 V

Frequency

60 Hz

Current

<5 A

Top Cover Clearance to Combustibles

12 in

Top Cover Clearance to Non-Combustibles

12 in

Water Connection

Top Inlet Water Connection

1-1/2 in

Front Inlet Water Connection

1-1/2 in

Back Inlet Water Connection

1-1/2 in

Top Outlet Water Connection

1-1/2 in

Front Outlet Water Connection

1-1/2 in

Back Outlet Water Connection

1-1/2 in

Features

Features

82% Thermal Efficiency Means Lower Operating Costs.

Fan Assisted Combustion
  • The blower is built into the Low NOx burner assembly for Ultra-Low NOx readings that comply with SCQAMD rule1146.2 of 14 ng/j or 20 ppm.
Metal Venting
  • Rated Category I Appliance. Uses standard double wall type "B" vent.
  • Can be commonly vented with other Category I appliances.
  • Vent connects directly to the vent connector outlet.
  • No Draft hood or barometric damper required.
  • Perfect choice for retrofit and upgrade installations.
Water Connections
  • For ease of installation, all SBLs feature water connections on the top, front, and rear.
  • "Hydro Cannon" inlet water connection eliminates harmful scale buildup, extending the life of the product.
  • The front inlet connection must be used for the Hydro Cannon benefits.
Glasslined Tank
  • Glass is applie d after the complete tank has been assembled to give a seamless barrier against corrosion by hot water.
Installed Cost Savings
  • When multiple SBL units are exclusively used in a vent manifold, use the National Fuel Gas Code Table 13 Vent Sizing information to determine vent diameter than a natural draft water heater and specifications.
  • The SBL often uses a smaller vent diameter than a natural draft water heater which saves on installation cost.
Fully Automatic Digital Control with Safety Shutoff
  • Accurate, dependable control system.
  • Features a two speed blower control for smooth main burner light-off.
  • Manual reset gas shutoff device for added safety.
  • Maximum inlet gas pressure is 14" W.C. Minimum gas pressure is 3.5" W.C. Natural Gas.
Foam Insulation
  • Saves fuel, helps reduce standby heat loss.
Jacket
  • Heavy gauge steel finished with a baked enamel finish over a bonderized undercoat.
Easy Cleaning
  • Handhole cleanout allows access for easy cleaning.
Fully Tested for Safety and Performance.
  • Design certified by the Underwriters Laboratory for 180 ºF hot water service.
  • Meets rigid requirements of the National Sanitation Foundation when equipped with optional leg kit.
  • Certified for use on combustible flooring.
Intermittent Ignition Device
  • Eliminates standing pilot.
  • Provides flame failure response in less than one second.
  • Spark ignitor and power ON/OFF switch.
Easy-to-Install
  • Completely factory-assembled.
  • Only gas, water, vent and electric connections need be made.
  • Provided with drain valve.
Anodes
  • Long-life, stainless steel core anode rods.
Plug Kits
  • Pipe nipples and caps are included to plug unused water connections.
NSF Leg Kit.
  • Meets NSF Standard 5 with optional leg kit - Part #9008214005.

Testing and Certifications

Testing and Certifications

Approval Ratings and Certification
  • All models meet ANSI Z21.10.3 - CSA 4.3 standards and the thermal efficiency and standby loss requirements of the U.S. Department of Energy and current edition of ASHRAE/IESNA 90.1

Other Features

Other Features

  • Integral automatic gas shutoff system prevents excessive water temperature
  • CSA Certified and ASME Rated T&P Relief Valve are factory-installed
  • Maximum working pressure is 160 psi standard
  • Adjustable thermostat with a 120 to 180 ºF range
  • All models certified up to 7,700 ft

Warranty

Warranty

  • 3-Year Limited Tank Warranty / 1-Year Limited Parts Warranty.

Note

Note

"A" after model number designates ASME construction.

Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.

Models available for sale in California only.