Catalog
For medium-demand commercial applications, State Titan™ (GPG and GPV) commercial gas water heaters offer precise power burner performance, plus flexible venting options including conventional atmospheric venting, sidewall venting or direct venting. Professional start-up service is also available from State on these Titan™ units to help ensure optimum performance.
Unit of Measure

Specifications

Manufacturer

N/A State®

Input Power

N/A 740000 BTU/hr

Tank Capacity

N/A 321.7 L

First Hour Rating at 100 ºF Temperature Rise

N/A 2944.7 L

Type

N/A Natural Gas

Style

N/A State Titan®

Size

N/A C

Industry Standards

N/A AHRI Certified® ASME Certified CSA® Certified Start-Up UL® Listed

Maximum Working Pressure

N/A 160 psi

Maximum Recovery

Recovery at 4 ºC Temperature Rise

N/A 6790.3 L/h

Recovery at 56 ºC Temperature Rise

N/A 2717.6 L/h

Recovery at 78 ºC Temperature Rise

N/A 1937.9 L/h

Dimensions

Schematic

N/A
Schematic Drawing for Titan™ Power Burner Low NOx Commercial Gas Water Heaters (GPV Models)

Features

Features

N/A Powered Gas Low NOx Burner (Natural Gas Only)
  • Premix burner operation includes internal Flue Gas Recirculation (FGR).
  • Safety features: Internal blocked flue sensor, separate pilot system, internal thermal cutoff and anti-flashback barrier.
Three Venting Options
  • Conventional atmospheric venting on GPG models only with supplied barometric draft regulating damper.
  • Horizontal atmospheric sidewall venting or direct venting on GPV models only.
  • For sidewall venting order Vent Kit Part # 9500007229.
  • For direct venting order Vent Kit Part # 9910001005.
Automatic Controls
  • Safety shut-off, high-temperature limit control.
  • Dual thermostat for accurate temperature adjustment from 120 ºF to 180 ºF.
Patented "Dome Design" Combustion
  • Draft-equalizing dome balances pressure inside combustion chamber for optimum flue loading and efficient heat transfer.
Adjustable Damper for High-Altitude Installations
  • Air intake damper easily reset for high-altitude installation by authorized start-up agent.
ASME Tank Construction - Rated Working Pressure 160 psi

Factory-Installed CSA Certified and ASME Rated T & P Relief Valve

Glasslined Tank
  • With multiple anode rods for long-term protection against corrosion.
Flame Inspection Port

Handhole Cleanout
  • For easy removal of sediment from tank bottom.

Testing and Certifications

Testing and Certifications

N/A
  • Meets the thermal efficiency and standby loss requirements of the U.S. Department of Energy and current edition of ASHRAE/IESNA 90.1
  • The GPG85 540 and 650 comply with SCAQMD 1146.2. The GPG85 740 meets low NOx code requirements for Texas and California requiring less than 40 ppm

Warranty

Warranty

N/A
  • 3-Year Limited Tank Warranty.

Note

Note

N/A Based on 80% Thermal Efficiency obtained in State engineering laboratories.

To compensate for effects of high altitude above 2,000 feet, recovery ratings should be reduced 4% for every 1,000 feet above sea level.

Current Draw (120V, 60Hz, 1 Phase): 5.0 amps, use 15 amps supply power.

Minimum gas supply pipe size is 1 1/4".

Maximum supply gas pressure 14" W.C.